Register Name Address Description
BAUDRATE 40007 Designates the baud rate used by the
MODBUS interface. After moding this
register, a gateway reset must be per-
formed before changes can take effect.
Value Represented Baud Selected
0 2400
1 4800
2 9600
3 (DEFAULT) 19200
4 38400
5 57600
6 115200
COMMODE 40008 Designates the operating mode used by
the MODBUS interface. After moding
this register, a gateway reset must be per-
formed before changes can take effect.
Value Represented Meaning
0 RTU : 8-N-2
1 (DEFAULT) RTU : 8-N-1
2 RTU : 8-E-1
3 RTU : 8-0-1
4 ASCII : 7-N-2
5 ASCII : 7-E-1
6 ASCII : 7-O-1
ADDRESS 40009 Designates the MODBUS Address used
in the communications interface. Values
range from 1-247. Default value is 99.
Modifying this register will result in a gate-
way reset.
Once you have written your new settings, you will have to
perform a reset for the settings to take effect.
To perform a reset, write the “RST_DEVICE” Gateway Coil @
address 3 to TRUE. The device will reset one second after
receiving this command. Your new communication settings will
be in effect.
To verify them, attempt to read the Gateway ID from registers
40002 - 40003